Показать сокращенную информацию

dc.contributor.authorСеливерстов, Г. И.
dc.contributor.authorЛычев, П. В.
dc.contributor.authorСавкова, Т. Н.
dc.contributor.authorДедолко, М. В.
dc.contributor.authorСавенок, В. М.
dc.contributor.authorЖуковский, А. А.
dc.coverage.spatialГомельru_RU
dc.date.accessioned2025-09-30T10:05:42Z
dc.date.available2025-09-30T10:05:42Z
dc.date.issued2025
dc.identifier.citationСнижение недоотпуска электроэнергии и повышение надежности электроснабжения потребителей за счет применения реклоузеров в сельских электрических сетях 10 кВ Гомельского района / Г. И. Селиверстов, П. В. Лычев, Т. Н. Савкова [и др.] // Вестник Гомельского государственного технического университета имени П. О. Сухого. – 2025. – № 3. – С. 75–81.ru_RU
dc.identifier.urihttps://elib.gstu.by/handle/220612/42757
dc.description.abstractПроанализированы состояние, проблемы и потенциал снижения недоотпуска электроэнергии и повышение надежности электроснабжения потребителей за счет применения реклоузеров в сельских электрических сетях 10 кВ Гомельского района. Приведены варианты места установки реклоузеров: одного реклоузера – при последовательном секционировании линии электропередачи с односторонним питанием и трех реклоузеров – в линии электропередачи с резервированием питания. Определены критерии оптимизации выбора места установки реклоузеров в сети: количество отключений потребителей фидера (линии или участка линии), длительность перерывов электроснабжения потребителей данного фидера, величина недоотпуска электрической энергии потребителям. Установлено, что для варианта установки трех реклоузеров с резервированием питания годовой недоотпуск электроэнергии снижается на 88,6 % по сравнению с базовым вариантом (без установки реклоузеров) и более чем в 3,3 раза, если сравнивать с вариантом установки одного реклоузера на линии электропередачи.ru_RU
dc.description.abstractThe article analyzes the status, problems and potential for reducing undersupply of electric power and increasing the reliability of consumer power supply through the use of reclosers in 10 kV rural electric networks of the Gomel region. The article presents options for installing reclosers: one recloser for sequential sectioning of a power transmission line with one-way power supply and three reclosers in a power transmission line with power supply redundancy. The criteria for optimizing the choice of recloser installation location in the network are defined: the number of disconnections of feeder consumers (line or line section), the duration of power supply interruptions for consumers of this feeder, the amount of undersupply of electric power to consumers. It has been established that for the option of installing three reclosers with power supply redundancy, the annual undersupply of electric power is reduced by 88.6% compared to the baseline option (without reclosers installation) and more than 3.3 times when compared to the options for installing one recloser on a power transmission line.
dc.language.isoruru_RU
dc.publisherГГТУ им. П.О. Сухогоru_RU
dc.subjectРеклоузерru_RU
dc.subjectНедоотпуск электроэнергииru_RU
dc.subjectОтключения потребителейru_RU
dc.subjectНадежность электроснабжения потребителейru_RU
dc.subjectRecloserru_RU
dc.subjectUndersupply of electricityru_RU
dc.subjectNumber of consumer outagesru_RU
dc.subjectDuration of consumer outageru_RU
dc.subjectReliabilityru_RU
dc.titleСнижение недоотпуска электроэнергии и повышение надежности электроснабжения потребителей за счет применения реклоузеров в сельских электрических сетях 10 кВ Гомельского районаru_RU
dc.title.alternativeReduction of undersupply of electricity and increase of reliability of electricity supply to consumers by using reclosers in rural 10 kV electrical networks of Gomel regionru_RU
dc.typeArticleru_RU
dc.identifier.udc621.316.1.05
local.identifier.doi10.62595/1819-5245-2025-3-75-81


Файлы, содержащиеся в ресурсе

Thumbnail

Располагается в коллекциях: