Показать сокращенную информацию
Обобщенные расчетные зависимости для определения интенсивности теплообмена при кипении смесевых хладагентов
dc.contributor.author | Овсянник, А. В. | |
dc.contributor.author | Макеева, Е. Н. | |
dc.coverage.spatial | Москва | |
dc.date.accessioned | 2016-03-02T07:55:48Z | |
dc.date.available | 2016-03-02T07:55:48Z | |
dc.date.issued | 2015-12 | |
dc.identifier.citation | Овсянник, А. В. Обобщенные расчетные зависимости для определения интенсивности теплообмена при кипении смесевых хладагентов / А. В. Овсянник, Е. Н. Макеева // Холодильная техника. - 2015. - № 12. - С. 33-37. | ru_RU |
dc.identifier.uri | https://elib.gstu.by/handle/220612/14154 | |
dc.description.abstract | Приведены результаты экспериментального исследования теплообмена при пузырьковом кипении смесевых хшдагентов R404A, R407C и R4I0A на оребренных трубах. Эксперименты проводились при температурах насыщения 13...28,5 "С. Экспериментально и теоретически установлено, что при развитом пузырьковом кипении интенсивность теплоотдачи не зависит от типа и профиля неизотермической оребренной поверхности, а определяется только режимными параметрами, метафизическими свойствами жидкости, геометрическими размерами оребренной поверхности и внутренними характеристиками процесса кипения. Коэффициенты теплоотдачи при кипении фреонов на оребренной поверхности значительно выше, чем на гладкой, т.е. при развитом пузырьковом режиме кипения теплообмен на такой поверхности в 2—4раза выше, чем на гладкой. Установлены эмпирические зависимости, позволяющие найти коэффициент теплоотдачи при кипении R404A, R407C и R410A на оребренной поверхности в условиях большого объема, удовлетворительно согласующиеся с экспериментальными данными с погрешностью 15—20%, что говорит о возможности применения полученных зависимостей для расчета теплообменпых аппаратов испарительного типа с сребренными поверхностями. | ru_RU |
dc.description.abstract | The results of the experimental research of the heat exchange at bubble boiling of R404A, R407C and R4I0A re frigerants on finned tubes are cited. 'The experiments were carried out at 13. ..28,5 "C saturation temperatures. It was established by experiments as well as theoretically that at the developed bubble boiling the intensity of the heat transfer didn 't depend on the type orprofile of the nonisothermicfinned surface but it was defined only by operation parameters, thermophysical properties of the liquid, geometrical dimensions of the finned surface as well as by the internal char acteristics of the boiling process. The heat transfer coefficients at the refrigerant boiling on a finned surface was rather higher than on the smooth one, i.e. at developed bubble boiling the heat exchange on finned surfaces was 2—4 times higher than on the smooth ones. The empiric dependences were defined that allowedfindingthe heat transfer coefficient at R404A, R407C and R4 IDA refrigerants boiling on the finned surface of a big volume; they were satisfactorily agreed with the experimental data, the error was 15—20%. The possibility of using the derived dependences to calculate heat exchange apparatuses of the evaporating type with finned surfaces was shown. | |
dc.language.iso | ru | ru_RU |
dc.publisher | Эко-Вектор | ru_RU |
dc.subject | Теплообмен при кипении | |
dc.subject | Парообразование | |
dc.subject | Интенсивность теплообмена | |
dc.subject | Коэффициент теплоотдачи | |
dc.subject | Оребренные поверхности | |
dc.subject | Испаритель | |
dc.subject | Теплообменный аппарат | |
dc.subject | Холодильная установка | |
dc.subject | Эмпирическая зависимость | |
dc.subject | Heat exchange at boiling | |
dc.subject | Vaporization | |
dc.subject | Mixed ozone safe refrigerant | |
dc.subject | Heat exchange intensity | |
dc.subject | Heat transfer coefficient | |
dc.subject | Finned surfaces | |
dc.subject | Evaporator | |
dc.subject | Heat exchange apparatus | |
dc.subject | Refrigerating plant | |
dc.subject | Empiric dependenc | |
dc.title | Обобщенные расчетные зависимости для определения интенсивности теплообмена при кипении смесевых хладагентов | ru_RU |
dc.title.alternative | Generalized calculated dependences to define the heat exchange intensity at boiling of mixed refrigerants | |
dc.type | Article | ru_RU |
dc.identifier.udc | 536.24 | ru_RU |